Concord CXA
Downloads
Concord Brochure
PDF
Concord CXA Installation Guide
PDF
Concord CXS Installation Guide
PDF
Concord CXAP Installation Guide
PDF
Concord CXA/H, S/H & P/H
CAD Files
Visit our downloads section

Concord CXA & CXS

Ideal's Concord CXA range of heat only, floor standing, gas boilers are available in both natural gas and LPG. The open flued boilers also feature an atmospheric burner.

The units incorporate on/off automatic ignition via an intermittent pilot. The modern control fascia includes warning lights for boiler on; overheat lockout and burner lockout. Inside, gas valves and controls are factory fitted as standard.

The CXS range incorporates high/low operation to provide high system efficiency. The range gives the choice of easy to operate models with simple analogue control. Optional remote indication kits provide volt free contacts for boiler performance monitoring.

Both CXA and CXS ranges are available in 9 model sizes from 40 kW to 120 kW. The 110 kW and 120kW models are suitable for installation in modular configurations – just 6 boilers can provide up to 720 kW output.

The CX range can be fitted onto induced-draught, fan dilution and mono-draught flue systems.

Efficiency

Models in this range operate between 82 and 84% energy efficiency

Features

  • 16 models with outputs 40 to 120 kw
  • Natural gas or propane
  • Automatic ignition
  • On off operation
  • Status lights indicating boiler on, overheat and lockout
  • 6 bar working pressure
  • Modern appearance
  • Anticycling and frost protection built in
  • Integrated low NOx design (class 3)

Specification

  • General Data
  • Dimensions & Clearances
  • Option Kits
Model 40/H
40P/H
50/H
50P/H
60/H
60P/H
70/H
70P/H
80/H
80P/H
90/H
90P/H
100/H
100P/H
110/H120/H
No. of sections 344556677
Output 405060708090100110120
Flow/return connectionsBSPRC2
Gas inletBSPRC¾RC¾RC¾RC¾RC¾RC1RC1RC1RC1
Flue sizemm150150175175200200200250250
Maximum working pressurebar6
Water contentL223030373745455353
Dry weight (approx)kg210265265330330395395490490
Seasonal Efficiency (Ref L2)%83.5683.4483.2882.4482.6083.6982.1683.5784.84
Model 40/H
40P/H
50/H
50P/H
60/H
60P/H
70/H
70P/H
80/H
80P/H
90/H
90P/H
100/H
100P/H
110/H120/H
Heightmm1000
Widthmm600
Depthmm750882882104210421212121213851385
Boiler Clearances (mm)Front750
Back000150150300300300300
Side50505050501000100010001000
  • Volt free contacts, boiler run, overheat & lockout
  • Down draft thermostat kit
  • Header kits (available from merchants)
  • Propane models (CXA only)