Concord ESi

The Concord ESi is a sectional cast iron boiler, with an atmospheric two stage gas burner and electronic ignition via an ignition burner. The heat output is adjustable to 85% of full the output. The Concord ESi is suitable for natural gas only.

The combustion chamber and draught diverter are designed for use with a hot water central heating system and have a heat output range of 119-380 kW which must be connected to a chimney.

The heat exchanger can be supplied assembled, or unassembled for site assembly.

The boiler is supplied with a control panel for one and two stage burner operation. It offers boiler control by two thermostats for high/low operation, indicator lights, overheat safety thermostat and thermometer giving boiler flow temperature.

Efficiency

Models in this range operate between 82 and 84% energy efficiency

Features

  • 9 models with outputs 140 to 380 kW
  • High/low adjustable operation on all models
  • Assembled or unassembled heat exchanger availability
  • Robust cast iron heat exchanger
  • Easy to install and service
  • Low return temperature capability
  • High full & part load efficiencies – meeting new Building Regulations

Specification

  • General Data
  • Dimensions & Clearances
  • Option Kits
Model 140160180200220260300340380
No. of sections 8910111214161820
Output 140160180200220260300340380
Flow/return connectionsBSPRC2
Gas inletBSPRP1RP1RP1RP1RP1RP1¼RP1¼RP1¼RP1½
Flue sizemm250250300300300350350350400
Maximum working pressurebar6
Water contentL6168768491106122137154
Dry weight (approx)kg575635690750805920103511501350
Seasonal Efficiency (Ref L2)%81.7182.0282.3382.6482.8783.1883.4483.6783.91
Model 140160180200220260300340380
Heightmm140614061406140614061406140614061406
Widthmm97010581146123413221498167418502026
Depthmm136213621362136213621412141214121412
Boiler Clearances (mm)Front1000
Back500 (measured from rear edge of jacket)
Side400 at water connection side, 200 at non-connection side (RH or LH)
  • Hours run meter (1 or 2 hours)
  • Flue gas thermometer