Evomod Condensing Boilers
Downloads
Floor Standing Condensing Brochure
PDF
Evomod Installation Guide
PDF
Evomod
CAD Files
Visit our downloads section

Evomod 250-1000 kW

With premix burner technology and a stainless steel heat exchanger, the Evomod range of boilers are capable of high operating efficiencies and low emissions that contribute to reducing running costs and are certified to meet the requirements of the Boiler Efficiency Directive.

The Evomod range introduces fully condensing modular benefits to higher outputs in a steel frame of up to 3 high stacking, providing minimum floor area that makes access through a standard (700mm frame width) doorway possible. When required in a difficult area of installation, the modular construction of the frame can be broken down into individual heat exchanger modules.

Each module provides a maximum of 250 kW heat output and will modulate down through a sophisticated control system. In this way a decreasing load is continuously matched for optimum efficiency, by modulating one module at a time.

Available in 250, 500, 750 and 1000 kW, the Evomod will achieve an output up to 1mW from a single unit solution together with a minimum footprint that enables the product to be installed where space is limited.

Installation of the range is made easier as the Evomod has smaller parts and is lighter in weight than many other floor-mounted boilers. The option of assembled, or on-site assembly also adds to this. Maintenance is also made simple through the boilers' valved header kits.

The Evomod range comes complete with two years parts and labour warranty as standard and - as with all products from Ideal Commercial - is completely manufactured and built in the UK.

Efficiency

90-91.3% energy efficiency (A)

Features

  • Wide range of model outputs
  • Modular boiler benefits:
    • Heat maintained during service
    • Easier installation as lighter, smaller parts
  • High efficiency
  • High modulation & close load matching (5:1 up to 20:1)
  • Low NOx emissions (<40mg/kWh)
  • Compact & minimum floor area
  • Simple controls interface with large backlit display
  • Module sequencing standard
  • Valved header kits for easy maintenance
  • Assembled and site assembly capability
  • Single flue, system, gas & electrical connections
  • Quality product through design, component selection and proving
  • 2 year warranty
  • Made in the UK

Specification

  • Performance Data
  • General Data
  • Dimensions & Clearances
  • Option Kits
Model 2505007501000
Output (Non Condensing)
Mean 70°C
MaxkW232.5465697.5930
Btu/hr793,3781,586,7742,350,1843,173,512
MinkW46.746.746.746.7
Btu/hr159,325159,325159,325159,325
Output (Condensing)
Mean 70°C
MaxkW252.5505757.51010
Btu/hr861,5301,723,0602,584,5903,446,120
MinkW51.451.451.451.4
Btu/hr175,404175,404175,404175,404
Boiler Input Max RateNetkW238476714952
Btu/hr812,0561,624,1122,486,1683,248,224
GrosskW264.1523.2792.31056.4
Btu/hr901,1091,802,2182,703,3273,604,436
Boiler Input Min RateNetkW47.647.647.647.6
Btu/hr162,411162,411162,411162,411
GrosskW52.852.852.852.8
Btu/hr180,256180,256180,256180,256
Gas RateMax Ratem3/hr25.250.475.6100.8
ft3/hr889.91779.82,669.73,559.6
Approx. Flue Gas
Volume @ 80°C
Max Rate i.e.
non-condensing
m3/hr39178311741566
ft3/hr13,80827,61541,45955,303
Max. Flue ResistancePa105105105105
Flue Gas CO2
G20/LNG
@ Max Rate%9.1 ±0.29.1 ±0.29.1 ±0.29.1 ±0.2
@ Min Rate%8.4 ±0.28.4 ±0.28.4 ±0.28.4 ±0.2
NOx with O2 = 0%mg/kWh39.739.739.739.7
ppm22.522.522.522.5
Seasonal Boiler Efficiency(Building Regs L2)%95.995.995.995.9
Model 2505007501000
Gas Supply 2H - G20 - 20mbar
Gas Supply Connection(in. BSP)R1¼R2R2R2½
Flow Connection(in. BSP)2½" PN165" PN165" PN165" PN16
Return Connection(in. BSP)2½" PN165" PN165" PN165" PN16
Hydraulic Resistance @ 20°C
(with optional water header pack fitted)
mbar100105110120
Max Press (sealed system)bar (psi)6 (87)6 (87)6 (87)6 (87)
Maximum Static Headm (ft)61 (200)61 (200)61 (200)61 (200)
Boiler Electricity Supply 230V - 50Hz
Boiler Fuse Rating 1x 5A Internal2x 5A Internal3x 5A Internal4x 5A Internal
Power Consumption
(boiler only)
W35068010201350
Air Inlet (optional)O/D mm300300300300 x2
Flue Size diamm150250250300
Condensate Drainmm21.52x 21.53x 21.54x 21.5
Boiler Dry Weight
(unpacked exc. headers)
kg (lb)229420611845
Water Contentl (gal)14.8 (3.26)29.6 (6.52)44.4 (9.78)59.2 (13.0)
IP Rating IP20

Electricity supply and Fuse rating for pumps etc. refer to manufacturer's instructions.

Note: Natural gas consumption is calculated using a calorific value of 37.8MJ/m3 (1038Btu/ft3) gross or 34 MJ/m3 (910 Btu/ft3) nett at 15°C and 1013.25 mbar.
a. For l/s divide the gross heat input (kW) by the gross C.V. of the gas (MJ/m3)
b. For ft/h3 divide the gross heat input (Btu/h) by the gross C.V. of the gas (Btu/ft3)
c. For M3/h multiply L/S by 3.6.

Model 2505007501000
Heightmm860148021001428
Widthmm7107107101420
Depthmm1339133913391339
Depth inc. Headers & Fluemm1775211821182118

Optional kits

  • Water & gas header assembly packaged
  • Water & gas header assembly c/w valves packaged
  • Water connection kit (250)
  • Air inlet collar

Included as standard

  • Remote indication (run & alarm)
  • Hours run
  • BMS (0-10v) operation
  • Pump overrun
  • Large backlit LCD controls (including 5 line plain text display)