Falcon
Downloads
Pressure Jet Brochure
PDF
Falcon GTS Installation Guide
PDF
Falcon GTS Users Guide
PDF
Falcon GTS
CAD Files
Visit our downloads section

Falcon GTS

The Falcon GTS range of cast iron sectional pressure jet boilers offer high efficiency operation, ease of maintenance, fuel flexibility and low emissions in a compact package.

Suitable for oil or gas operation the Falcon GTS is supplied in a choice of 5 standard models, rated in outputs from 40 kW to 100 kW the range has a maximum operating pressure of 4 bar. The GTS 7 and GTS 8 may be high/low operation.

Designed with a large combustion chamber and 3 pass, horizontal flue way incorporating fins and cast iron turbulators, the Falcon GTS ensures maximum heat transfer efficiency.

The boilers are suitable for combined indirect pumped domestic hot water, central heating systems, independent indirect pumped domestic hot water and central heating systems.

Fully pumped systems may be open vented or sealed.

Efficiency

Models in this range operate between 84 and 88% energy efficiency

Features

  • 5 models with outputs 36 to 102 kW
  • Fuel flexibility – Natural gas or oil
  • High efficiency 93% net (84% gross)
  • 3 pass heat exchanger
  • Compact size
  • Minimal emissions
  • Comprehensive control
  • Easy to install and service
  • Low temperature return
  • Striking appearance

Specification

  • General Data
  • Dimensions & Clearances
  • Option Kits
Model GTS 4GTS 5GTS 6GTS 7GTS 8
Sections 45678
OutputkW40 - 5050 - 6464 - 7878 - 9292 - 100
Flow/Return ConnectionsBSPR1¼R1¼R1½R1½R1½
Flue Sizemm153153180180180
Maximum Working Pressurebar4
Water ContentL3643505764
Dry Weight (Approx)kg254296344381423
Seasonal Efficiency(gas) %84.3784.5484.7984.7784.83
(oil) %87.7087.9088.2088.2088.20
Model GTS 4GTS 5GTS 6GTS 7GTS 8
Heightmm1100
Widthmm520
Depthmm772899102611531280
Boiler Clearances (mm)Front1000
Back500
Left500
Right
  • DHW sensor