Harrier GTS boilers are cast iron sectional pressure jet boilers offering high efficiency operation, ease of maintenance, fuel flexibility and low emissions.
Suitable for oil or gas operation the Harrier GTS range is supplied in a choice of 5 standard models, rated in outputs from 105 kW to 330 kW and has a maximum operating pressure of 6 bar. All models may have high/low operation.
Designed with a large combustion chamber, 3 pass horizontal flue ways, incorporating fins and cast iron turbulators, the Harrier GTS ensures maximum heat transfer efficiency (up to 91.5% nett).
The boilers are suitable for combined indirect pumped domestic hot water and central heating systems, independent indirect pumped domestic hot water or central heating systems.
Fully pumped systems may be open vented or sealed.
| Model | GTS 5 | GTS 6 | GTS 7 | GTS 8 | GTS 9 | |
|---|---|---|---|---|---|---|
| Sections | 5 | 6 | 7 | 8 | 9 | |
| Output | kW | 140 | 180 | 230 | 280 | 330 |
| Flow/Return Connections | DN flange | 65 | ||||
| Flue Size | mm | 180 | 180 | 200 | 200 | 200 |
| Maximum Working Pressure | bar | 6 | ||||
| Water Content | L | 116 | 136 | 156 | 176 | 196 |
| Dry Weight (Approx) | kg | 736 | 846 | 981 | 1103 | 1230 |
| Seasonal Efficiency | (gas) % | 83.87 | 84.00 | 84.55 | 84.64 | 84.82 |
| (oil) % | 87.20 | 87.40 | 87.90 | 88.00 | 88.20 | |
| Model | GTS 5 | GTS 6 | GTS 7 | GTS 8 | GTS 9 | |
|---|---|---|---|---|---|---|
| Height | mm | 1297 | ||||
| Width | mm | 800 | ||||
| Depth (including connections) | mm | 1151 | 1311 | 1471 | 1631 | 1791 |
| Boiler Clearances (mm) | Front | 1500 | ||||
| Back | 1000 | |||||
| Side (non hinge) | 100 | |||||
| Side (door hinge) | 500 or 200 + burner length | |||||