Imax Plus III
Downloads
Floor Standing Condensing Brochure
PDF
Imax Plus III Users Guide
PDF
Imax Plus III Installation Guide
PDF
Imax Plus III
CAD Files
Visit our downloads section

Imax Plus III

The Imax plus III offers greater flexibility of installation and operation with outputs from 95kW to 330kW in a range of six compact floor standing boilers. The range can be installed in multiple formation to provide even larger outputs if the system requires.

The fully modulating gas/air design ensures maximum efficiency is maintained down to as low as 11.2kW output, achieved even with the largest model as the unique design optimises load matching.

Each boiler comprises several sections, each flueway or module having its own burner, fan, gas valve, ignition and safety controls. As system load decreases the boiler modulates down to the combined minimum. As load further decreases modules are switched off to further match the reducing load. Wasteful boiler cycling is minimised whilst stand-by back up is built into the design.

The range is designed for ease of installation ensuring boiler house siting is as simple and as fast as possible. The Imax plus III is also the quietest boiler of its size at less than 50dBA. Naturally the range is NOx class 5.

Advanced microprocessor based controls are used to operate all electrical functions and provide full commissioning and fault diagnostic displays.

The units also include Hours Run Meters and BMS control built-in, along with weather compensation supplied as standard.

Efficiency

All models in this range operate above 94.5% energy efficiency

Features

  • Range of six models from 95 – 330kW
  • Compact size – small footprint
  • High modulation – close load matching (all models down to 11.2kW)
  • 106.8% Net efficiency (fully condensing) at 30% part load
  • Boilers consist of several modules giving built-in standby capability
  • Robust cast-aluminium heat exchanger
  • Integral commissioning and fault diagnostics
  • Optional flue and system connections for fast installations
  • Outside and DHW sensors supplied as standard
  • Meets Building Regulations 2010 (Part L2)

Specification

  • General Data
  • Dimensions & Clearances
  • Option kits
Model F95F145F190F235F285F330
Boiler output (condensing) 50/30°C 12.7 - 95.9 12.7 - 144.1 12.7 - 192.4 12.7 - 241.0 12.7 - 289.9 12.7 - 339.4
Boiler output (condensing) 80/60°C 11.2 - 93.2 11.2 - 140.0 11.2 - 197.0 11.2 - 234.7 11.2 - 282.2 11.2 - 329.5
Flow/Return ConnectionsBSPR2
Gas InletBSPR1½
Flue Sizemm150150150200200200
Maximum Working Pressurebar6
Water ContentL10.114.218.322.426.530.6
Dry Weight (Approx)kg156191230272312357
Seasonal Efficiency (Ref L2)%94.5794.6094.6594.6994.7294.73
Model F95F145F190F235F285F330
Heightmm1053
Widthmm69569583496811021236
Depthmm695
Boiler Clearances (mm)Front600
Back450450450450450450
Side50 (1 side) & 450 (other side), increase to 600 for side flues.
  • Air inlet socket and blanking plate kit
  • 6 Cascade manager
  • Left or rear condensate level harness kit (190-330 models only)