- 2 year parts and labour warranty
- All the Logic HIUs incorporate a spacer piece which can be easily removed and a heat meter fitted inside the unit. This allows the energy used by each individual apartment to be recorded and charged accordingly
- Twin plate design hydraulically separates both domestic and space heating from the central primary supply
- Pump bypass protection, in case of complete radiator TRV shutdown
- Compact and lightweight
- Fully insulated EPP front cover
- Convertible to underfloor heating
- Ability to pre-heating of the DHW exchanger

Logic Heat Interface Units (HIU) Indirect - 50 Indirect
The Ideal Heat Interface Units (HIU) are heat energy transfer units, designed for use in conjunction with centralised boilers, district heating or central energy systems. The function is to efficiently transfer heat from
the plant room to the individual dwellings central heating (CH) and domestic hot water (DHW) systems.
The Logic Indirect HIUs are the latest 'intelligent’ range of HIU from Ideal. The Logic HIU is the complete solution for instantaneous hot water production and space heating control. The indirect wall mounted HIU,
providing instantaneous priority direct hot water (DHW) and modulated central heating (CH). This can be converted to under floor heating including inbuilt safety thermostat capability.

FEATURES & BENEFITS
- Compact Wall Hung
- 2 Year Warranty
- Erp Prepared
SPECIFICATIONS
Logic Heat Interface Units (HIU) Indirect 50 Indirect
Height | 630 mm |
Width | 550 mm |
Depth | 265 mm |
Heating Set Point | 25-75°C |
Nom. heating exhangner net output | 15 kW |
Secondary circuit (Max pressure rating) | 3 bar |
Secondary circuit (Max operating pressure) | 2.5 bar |
Pump UPS | 15/60 |
Pump bypass setting | 0.45 bar |
Pressure switch opening | 0.4 bar |
Pressure switch closing | 0.8 bar |
Safety relief valve setting | 3 bar |
Safety thermostat | 55°C ±3 |
Expansion vessel | 7.5 litre |
Under floor heating capability | Optional |
Heating control cicuit | VOLT FREE |
Maximum working pressure (primary) | 16 bar |
Maximum working pressure (secondary) | 3 bar |
Maximum temperature | 85°C |
Max. percentage of glycol | 30% |
Max. recommended primary cicuit flow rate | 1.2 m³/h |
Min. differential pressure on domestic water modulating valve | ^p 0.35 bar |
Set Point DHW temperature | 42 to 60°C |
Max. Domestic hot water pressure | 10 bar |
DHW cicuit max. flow rate | 18 l/m |
Min. flow rate to activate domestic flow sensor | 2.7 l/m |
Max. Differential pressure on domestic water modulating valve | 1.65 bar |
Nom. DHW heat exchanger net output | 50 kW |
Power supply | 230 V (ac)±10% 50Hz |
Max power consumption | 105 W |
Protection class | IP 40 |
Actuator | stepper 24 V |
Probes | NTC 10 kΩ |
Frame | RAL 9010 sprayed steel |
Protective shell cover | EPP (Expanded polypropylene) |
Components | brass BS EN 12165 CW617N |
Pipes | stainless steel |
Exchanger | brazed stainless steel |
Standard and Optional kits
Optional
- CF ECHO II ultrasonic meter
- CF ULTRAMAXX V ultrasonic meter
- Flushing Bypass