Super Series 4

Similar Products

Downloads
High Efficiency Brochure
PDF
Super Series 4 Installation Guide
PDF
Super Series 4
CAD Files
Visit our downloads section

Super Series 4

The Super Series 4 comprises identical 50kW modules with heat outputs from 50kW to 600kW, with the number of modules in use dependent on the maximum load. Fitted on slide rails, the modules are located in an insulated stainless steel boiler casing. The products of combustion first give up their heat to water flowing through the modules then are discharged.

The heat exchanger consists of extruded copper finned tubes in a circular arrangement around the gas burner. Copper tubes are expanded into cast iron headers, onto which cast iron cover plates are bolted.

Suitable for vertical or horizontal assembly, Super range installations can save over 30% of the typical plant room space normally used by conventional boilers.

Efficiency

Models in this range operate between 84 and 85% energy efficiency

Features

  • 19 models with outputs from 50-600kW
  • 50kW models
  • Vertical and horizontal models
  • High efficiency 85 % gross cv (94% nett cv)
  • Low NOx emissions (class 5)
  • Low noise
  • Compact size
  • Sequence controlled
  • 6 bar working pressure
  • Complete package – incorporating single flue outlet, gas and water heaters included
  • Remote indication contacts

Specification

  • Super Series 4 (50-300)
  • Super Series 4 (350-600)
  • Option Kits
Model 50/V100/V150/V150/VA200/V250/V250/H300/V300/H
Modules 123345566
OutputkW50100150150200250250300300
Heightmm78214321912148714871967144319721443
Widthmm439701701117111711171178311711783
Depthmm698
Flow/Return ConnectionsDN flange405065656580808080
Gas InletBSPRC¾RC1RC1¼RC1¼RC1¼RC1½RC1½RC1½RC1½
Flue Sizemm125175200200250250250300300
Maximum Working Pressurebar6
Water ContentL4.511.920.721.726.237.739.744.544.5
Dry Weight (Approx)kg82.1187.7274.1296.4348461411.2511.2513.7
Boiler Clearances (mm)Front950
Back25
Left450900
Right
Seasonal Efficiency (Ref L2)%84.5084.3984.7584.7684.9684.9684.9684.9684.96
Model 350/V400/V400/H450/V500/V500/H550/V550/H600/V600/H
Modules 7899101011111212
OutputkW350400400450500500550550600600
Heightmm1618161821441345214413452144134521441345
Widthmm1822182218332393183323931833239318332393
Depthmm1350
Flow/Return ConnectionsDN flange100100125125125125125125125125
Gas InletBSPRC2
Flue Sizemm350350400400400400450450450450
Maximum Working Pressurebar6
Water ContentL63.368.197.692.6102.497.4107.2102.2112107
Dry Weight (Approx)kg765813985972103310201080106711291115
Boiler Clearances (mm)Front950
Back950
Left1200
Right
Seasonal Efficiency (Ref L2)%84.96
  • Water flow switch for boiler protection in the event of pump failure
  • Module blanking off pack
  • External sequencer control kit